Solar Battery Backup Calculator (2026)
Enter your AC, extra load and the backup hours you want, and get the battery bank size in kWh and Ah — with LiFePO4 and lead-acid options costed side by side for Indian homes.
Overnight power-cut sizing
LiFePO4 vs lead-acid
Free · no sign-up
Tonnage
Star rating
Fans, lights, Wi-Fi, fridge
A typical bedroom set is 150–300 W.
200 W
Hours of power cut to cover
Summer power cuts in much of India cluster overnight — 8 hours covers 10 PM to 6 AM.
8 h
Advanced
Ah figures below are quoted at this bank voltage. AC-capable inverters are usually 24 V or 48 V.
How does it work?
- You enter the AC you want to run, any other load, and how many hours of backup you need.
- The AC's running draw = cooling capacity ÷ its ISEER — holding a set temperature overnight draws well under its nameplate watts.
- Energy needed = (AC draw + other load) × backup hours ÷ 90% inverter efficiency.
- Bank size = that energy ÷ the chemistry's usable depth of discharge: ~80% for LiFePO4, ~50% for flooded lead-acid.
- That is why the same backup needs a much bigger, heavier lead-acid bank — and why LiFePO4 usually costs less per cycle despite the sticker premium.
Prices are 2026 India market ballparks for the battery alone, excluding the inverter or PCU.